| Specifications |
|
|
|
AC Input: |
Single phase
(refer to RM18XX, RM20XX series brochures for full details)
|
Frequency Range: |
45-66Hz |
Power Factor: |
>0.99 (full load) |
Efficiency: |
>91% (>50% power output) |
Termination: |
Single phase, 10mm² L, N, E tunnel terminals |
|
|
DC Output |
|
Nominal Voltage: |
-48V, -60V (+24V available to special order) |
Rated System
Output Power: |
4000W
@ -48V |
Polarity: |
Positive earth (negative earth available to special order) |
DC Distribution: |
Load: 1x 63A load circuit breaker
Battery: 1x 63A battery circuit breaker |
Breaker Fail Detection: |
Electronic fail detection on both load and battery breakers |
DC Terminals: |
Tunnel terminals, 10mm² |
| Low Voltage Disconnect: |
80A battery LVD fitted as standard |
|
|
Mechanical |
|
Size: |
Width: 482.6mm (standard 19” module)
Height: 44.45mm (1U, 1¾”)
Depth: 350mm (13¾”) (390mm with cable strain relief) |
|
|
Monitoring &
Control: |
Various monitoring options are available via the Enatel SM30
series of control & supervisory modules. Standard features
include full temperature compensation, automated and manual
battery testing/equalisation and three voltage-free relay alarm
outputs. Options include extension I/O PCBs that give an extra
6x digital inputs, 6x analogue inputs and 8x voltage-free relay
outputs. For further details, refer to the SM30 series brochures. |