| Specifications |
|
|
|
AC Input: |
Single phase. |
| AC Current: |
170V AC, 15.0A max. 230V AC, 11.1A nominal
(refer to RM8xx, series brochures for full details) |
Frequency Range: |
45-66Hz |
Power Factor: |
>0.99 (full load) |
Efficiency: |
>91% (>50% power output) |
Termination: |
Single phase, 1.5m flying lead. |
|
|
Nominal Voltage: |
-48V (+24V available to special order). |
Rated System
Output Power: |
2400W max (50A @ -48V; 44.4A @ -54.0V) |
Polarity: |
Positive earth (negative earth available to special order). |
DC Distribution: |
Load: 2x 10A, 2x 20A load circuit breakers.
Battery: 1x 30A battery circuit breaker
(extra 30A battery breaker optional). |
Breaker Fail Detection: |
Electronic fail detection on both load and battery breakers. |
DC Terminals
(Front Connected): |
Load: 6mm² push-in spring cage.
Battery: 55A power-pole plug-in connectors (1 set, 2 optional). |
Low Voltage
Disconnect: |
50A battery LVD (magnetically latching) fitted as standard. |
|
|
Dimensions
(W,H,D): |
482.6mm (standard 19” module), also fits ETSI 515mm
mounting cabinet, 44.45mm (1U, 1.75”), 285mm (11.6”) |
Weight: |
5kg (excluding rectifier modules) |
|
|
Monitoring &
Control: |
Various monitoring options are available via the Enatel SM30
series of control & supervisory modules. Standard features
include full temperature compensation, automated and manual
battery testing/equalisation and three voltage-free relay alarm
outputs. Options include extension I/O PCBs that give an extra
6x digital inputs, 6x analogue inputs and 8x voltage-free relay
outputs. For further details, refer to the SM30 series of brochures. |
| Alarm Terminals: |
Voltage-free alarm terminal connections via front panel hi-density
D15 connector. |