| Specifications |
|
| |
|
|
AC Input:
|
Three phase
(refer to RM18XX, RM20XX series brochures for full details)
|
|
Frequency Range:
|
45-66Hz |
|
Power Factor:
|
>0.99 (full load) |
|
Efficiency:
|
>91% (>50% power output) |
|
Termination:
|
Three phase L1, L2, L3, N, E 10mm² terminal blocks
Surge protection (40kA 8/20msec) |
| |
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V, -60V (+24V available to special order) |
|
Rated System
Output Power:
|
14000W
@ -48V |
|
Polarity:
|
Positive earth (negative earth available to special order) |
|
DC Distribution:
|
Load: 2x 10A, 6x 32A, 2x 50A load circuit breakers
Battery: 4x 100A battery circuit breakers |
|
Breaker Fail Detection:
|
Electronic fail detection on both load and battery breakers |
|
DC Terminals:
(rear connected)
|
Load: 10A, 32A, 10mm² tunnel terminals
50A, 16mm² tunnel terminals
Battery: 35mm² tunnel terminals |
| Low Voltage Disconnect: |
400A battery LVD fitted as standard |
| |
|
|
Mechanical
|
|
|
Size:
|
Width: 482.6mm (standard 19” module)
Height: 222.2mm (5U, 8¾”)
Depth: 350mm (13¾”) (390mm with cable strain relief) |
| |
|
Monitoring &
Control: |
Various monitoring options are available via the Enatel SM30
series of control & supervisory modules. Standard features
include full temperature compensation, automated and manual
battery testing/equalisation and three voltage-free relay alarm
outputs. Options include extension I/O PCBs that give an extra
6x digital inputs, 6x analogue inputs and 8x voltage-free relay
outputs. For further details, refer to the SM30 series brochures. |